Fire
Sealed Sleeved Plug Valves
|
 |

See the Figure Number Selection Guide section of the catalog
for FluoroSeal plug valve availability. |
FluoroSeal Sleeved Plug Valves with the Fire Seal
top seal have been tested by an independent
laboratory to the requirements of API 607, fourth
edition and exceeded the requirements for external
leakage.
|
|
|
|


|
The FluoroSeal fire seal
design utilizes a PTFE sleeve and PTFE diaphragm as the
external sealing components under normal conditions. Should
these components be destroyed by fire, external leakage is
prevented by: |
|
1. A secondary flexible graphite seal ring encapsulated and
compressed between the metal diaphragm and the machined
counterbore in the valve body.
2. A flexible graphite delta ring encapsulated and compressed
between the unique shaped metal diaphragm and the machined
plug stem.
|
 |
 |
|
| FluoroSeal
fire seal valves also utilize a vented plug designed to
relieve pressure buildup resulting from expansion of the
service media, within the plug, due to elevated
temperatures caused by fire. The pressure is relieved to
the upstream side, resulting in a uni-directional valve,
which is indicated by an arrow on the side of the valve
body. |
|
 |
|
 |
|